PHONE : 982144972925-7+

YSLYCY

Code No. of cores External diameter Sheath thickness Cable weight Packing*
No
    Nx mm² .approx nominal .approx  
  mm mm kg/km  
Cross Section :0.5
4935 3 8.6 1 110 Cut
4945 4 9.4 1 130 Cut
4955 5 10.4 1.2 155 Cut
4975 7 11.1 1.2 180 Cut
49105 10 12.8 1.2 230 Cut
49125 12 13.9 1.2 300 Cut
49185 18 16.8 1.5 400 Cut
49255 25 19.5 1.8 520 Cut
49345 34 21.8 1.8 660 Cut
49505 50 26.1 2.1 950 Cut
49615 61 27.2 2.1 1065 Cut
Cross Section :0.75 
4937 3 9 1 120 Cut
4947 4 10.2 1.2 155 Cut
4957 5 10.9 1.2 180 Cut
4977 7 11.6 1.2 210 Cut
49107 10 13.6 1.2 290 Cut
49127 12 14.5 1.2 350 Cut
49187 18 17.6 1.5 465 Cut
49257 25 20.6 1.8 610 Cut
49347 34 23.5 1.8 810 Cut
49507 50 27.6 2.1 1120 Cut
49617 61 29.4 2.1 1300 Cut
Cross Section :1.0
4931 3 9.6 1 140 Cut
49410 4 10.6 1.2 175 Cut
49510 5 11.4 1.2 200 Cut
49710 7 12.1 1.2 235 Cut
491010 10 14.1 1.5 330 Cut
491210 12 16.4 1.5 430 Cut
491810 18 19.1 1.8 555 Cut
492510 25 22 1.8 720 Cut
493410 34 25.5 2.1 960 Cut
495010 50 29.5 2.1 1330 Cut
496110 61 31.5 2.4 1560 Cut
 
.Code No. of cores External diameter Insulation thickness Cable weight Packing*
No
    Nx mm² .approx nominal .approx  
  mm mm kg/km  
Cross Section :1.5
49315 3 1.6 1.2 175 Cut
49415 4 11.3 1.2 200 Cut
49515 5 12.1 1.2 240 Cut
49715 7 13.2 1.2 290 Cut
491015 10 15.2 1.5 420 Cut
491215 12 17.6 1.5 520 Cut
491815 18 20.3 1.8 675 Cut
492515 25 24.5 2.1 910 Cut
493415 34 27.5 2.1 1210 Cut
495015 50 32.1 2.4 1680 Cut
496115 61 34.1 2.4 1920 Cut
Cross Section :2.5
49325 3 11.8 1.2 12 Cut
49425 4 13.1 1.2 285 Cut
49525 5 14.3 1.2 350 Cut
49725 7 15.4 1.2 430 Cut
491025 10 17.4 1.8 560 Cut
491225 12 20.7 1.8 760 Cut
491825 18 24.8 2.1 1015 Cut
492525 25 28.9 2.1 1360 Cut
493425 34 33.1 2.4 1820 Cut
495025 50 39.8 2.7 2520 Cut
496125 61 41.2 2.7 2960 Cut
Temperature during installation: -5 °C up to +50 °C
fixed installed temperature : -30 °C up to +70 °C
Nominal voltage: Uo /U = 300/500 V
Test voltage: min. 4000 V
Insulation resistance: min. 20 MΩ x km
Min. inner bending radius: 6D
at application with bending: 20D
Behaviour in fire: IEC 60332-1

 

Electrical Specifications
Cross Section
mm2
Conductor resistance at 20 °C Current Carrying Capacity Insulation thickness Insulation
Resistance
0.5 39 6A 0.6  
0.75 26 13A 0.6  
1 19.5 16A 0.6 20 MΩ.km
1.5 13.3 20A 0.6  
2.5 7.98 25A 0.7  

 

Conductor: bare copper conductor, fine wired stranded, class 5 acc. to IEC 60228 / HD 383 / DIN VDE 0295
Insulation: PVC compound TI2 acc. to HD 21.1 / DIN VDE 0281 or YI2 acc. to VDE 0207.4, with green-yellow core, always in external layer (≥ 3 cores) or without green-yellow core
core marking: (acc. to DIN VDE 0293) black numbered or coloured
Inner sheath: PVC compound
Screen: braid of tinned copper , with min 85% Coverage
External sheath: PVC compound TM2 acc. to HD 21.1 / DIN VDE 0281 or YM2 acc. to VDE 0207.5
sheath colour: grey (RAL 7001) or transparent

Flexible signal cable used for surveillance and control of static or mobile devices in industry, electric plants or offices. Screen of braided copper wires serves as protection against electromagnetic impacts and signal disturbances. Lightweight and relatively thin, resistant to medium mechanical loads, used for fixed or limitedly mobile installations (not permanently mobile) without strain. Installed in dry or damp premises, outdoor application only under protection against UV-irradiation. Not intended for laying in ground or water.