Standard Fire Alarm Cable

Standard Fire Alarm Cable
  • Screen
  • Halogen Free
  • Low Smoke
  • Max Conductor Temperature 90ºC
  • Flame Retardant Acc to IEC60332-1-2
Dimensional Specifications
Part Number No. of Cores & Nominal Cross Section Area (Sq. mm) No. of Strands / Strand Diameter (mm) Nominal Overall Diameter (mm)
58215 2x1.5 7/0.52 9.5
58225 2x2.5 7/0.66 11
58315 3x1.5 7/0.52 10.1
58325 3x2.5 7/0.66 11.9
58415 4x1.5 7/0.52 11.1
58425 4x2.5 7/0.66 13
Electrical Specifications
Max. Conductor Resistance at 20°C (Ω/km) No. of Cores & Nominal Cross Section Area (Sq. mm) Part Number Voltage Drop DC or Single Phase AC (mV/A/m)
DC or Single Phase AC enclosed DC or Single Phase AC Clipped
12.1 17.5 20 29
7.41 24 27 18
12.1 17.5 20 29
7.41 24 27 18
12.1 17.5 20 29
7.41 24 27 18
Temperature Range
Working Temp - 40°C up to +90°C
Fixed Installed Temp - 40°C up to +50°C
 Short  Circuit Temp

 280°C

Mechanical And Electrical Specifications
Nominal Voltage 300/500V
Test Voltage 6.5 KV AC  5 min
 Min  Bending  Radius 6 برابر قطر کابل
Smoke Emition  IEC 61034; EN 61034-2
Flame Behavior IEC 60332-1; IEC 60332-3-24
Cable Standard BS 7629-1 -BS 5839-1  -BS EN 50200 
Conductor Stranded Copper Wire Class 2 Acc to IEC 60228 (Cross section : 1.5 , 2.5 mm2)
Insulation XLPE+Mica Tape
Color Code 2 Core : White - Blue
3 Core: Blue - white- Black
4 Core :Blue- White- Black- Brown
Screen Polyester Tape +tinned Copper Wire (Drain)+Aluminium Polyester Tape
Sheathing Halogen free Compound -Flame retardant and low Smoke
Color Red(Ral 3000)

Fire alarm cables are for use with fire monitoring/detection, power-limited fire alarm systems, smoke detectors, signaling, audio circuits, control circuits, fire protective circuits and security systems.