PHONE : 982144972925-7+

RE-Y(St)YQY PIMF

Code No. of cores External diameter Insulation thickness Cable weight Packing*
No.
    N x mm² approx. nominal approx.  
    mm mm kg/km  
Cross Section :0.5
Q2325 2 9,11 0.6 215 CUT
Q3245 4 10,61 0.6 300 CUT
Q3265 6 12,61 0.6 380 CUT
Q3275 8 13,71 0.6 445 CUT
Q32105 10 16,11 0.6 570 CUT
Q32125 12 16,61 0.6 680 CUT
Q32165 16 18,51 0.6 800 CUT
Q32205 20 20,61 0.6 915 CUT
Q32245 24 23,1 0.6 1065 CUT
Cross Section :0.75
Q3227 2 10,41 0.6 245 CUT
Q3247 4 12,51 0.6 350 CUT
Q3267 6 13,71 0.6 450 CUT
Q3277 8 14,81 0.6 515 CUT
Q32107 10 17,51 0.6 670 CUT
Q32127 12 18,11 0.6 715 CUT
Q32167 16 20,31 0.6 900 CUT
Q32207 20 22,51 0.6 1060 CUT
Q32247 24 25,11 0.6 1255 CUT
Cross Section :1.0
Q32210 2 10,51 0.6 290 CUT
Q32410 4 13,51 0.6 385 CUT
Q32610 6 14,81 0.6 510 CUT
Q32710 8 16,11 0.6 635 CUT
Q321010 10 18,91 0.6 770 CUT
Q321210 12 19,61 0.6 855 CUT
Q321610 16 21,81 0.6 1050 CUT
Q322010 20 24,41 0.6 1200 CUT
Q322410 24 27,31 0.6 1475 CUT
Cross Section :1.3
Q32213 2 11,31 0.6 315 CUT
Q32413 4 14,1 0.6 425 CUT
Q32613 6 14,51 0.6 615 CUT
Q32713 7 17,21 0.6 725 CUT
Q321013 10 20,31 0.6 885 CUT
Q321213 12 21,1 0.6 990 CUT
Q321613 16 23,51 0.6 1205 CUT
Q322013 20 26,21 0.6 1490 CUT
Q322413 24 29,81 0.6 1780 CUT
Cross Section :1.5
Q32215 2 11,61 0.6 335 CUT
Q32415 4 14,51 0.6 455 CUT
Q32615 6 16,31 0.6 655 CUT
Q32715 7 17,81 0.6 765 CUT
Q321015 10 21,1 0.6 935 CUT
Q321215 12 21,81 0.6 1055 CUT
Q321615 16 24,41 0.6 1315 CUT
Q322015 20 27,31 0.6 1600 CUT
Q322415 24 30,91 0.6 1945 CUT
Conductor
Resistance
Class2(MAX)
Insulation
Resistance
(MIN)
Mutual
Capacity
(MAX)
Flame
Propagation
L/R(RATIO)
(MAX)
Current
Load(25ºC)
Operating
Voltage
Test
Voltage
Bending
Radius
mm² Ω/km MΩxKm


5000
mm²  pF/m   mm² µH/Ω mm²  A 300/500 V.  Cr./Cr.=2000 V
Cr./Scrn.=2000 V 
8 X Cable Ø
0,50  36 0,50  100 IEC 60332-3-24 0,50  25 0,50  6,0
0,75  24,5 0,75  100 VDE 0482-332-3-24 0,75  25 0,75  13
1,0  18,1 1,0  100 EN 60332-3-24 1,0  25 1,0  16
1,3 13,9 1,3 100 BS EN 60332-3-24 1,3 40 1,3 18 
1,5 12,1 1,5 100   1,5 40 1,5 20
Conductor CU, Class 2 Acc to IEC 60228 / DIN VDE 0295 / EN 60228
Insulation EN 50290-2-21 PVC COMPOUND
Colour Code BS 5308-2 OR BLACK-WHITE; EACH PAIR NUMBERED
Individual Screen PES TAPE; TINNED COPPER DRAIN WIRE; AL-PES TAPE
Stranding PAIRWISE, SCREENED PAIRS IN LAYERS
Wrapping PES TAPE
Overall Screen TINNED COPPER DRAIN WIRE; AL-PES TAPE
Inner Sheath EN 50290-2-22 PVC COMPOUND
Armour GALVANIZED STEEL WIRE BRAIDING
Sheath EN 50290-2-22 PVC COMPOUND
Sheath Colour RAL 5015*BLUE / RAL 9005 BLACK
  • Instrumentation and control engineering analog and digital signal transmission
  • In chemistry industry
  • Petrochemistry industry
  • Power plants
  • Indoors and outdoors, dry, damp and wet environments
  • Gas Stations
  • Water Conveyance Systems

 

NOTES

  • EMC*: Electromagnetic compatibility
  • Fl*: Flame retardant outer sheath
  • Ral 5015 blue sheath*: At ex-proof connections in explosive and in flammable environments, intrinsically safe
  • Ral 9005 black sheath*: Places where UV resistance is required