PHONE : 982144972925-7+

RE-Y(St)YRY TIMF

(RE-Y(St)YRY TIMF (0.5-2.5
Code No. of Triple Armour Wire Diameter External Diameter Cable weight Packing*
.No
    Nx mm² .approx nominal .approx  
  mm mm kg/km  
Cross Section :0.5
3815 1 0.9 11.7 265 CUT
3825 2 0.9 16.2 430 CUT
3835 3 0.9 16.8 480 CUT
3845 4 0.9 18.3 555 CUT
3855 5 0.9 19.6 630 CUT
3865 6 1.25 21.7 830 CUT
3875 7 1.25 21.7 865 CUT
38105 10 1.25 26.7 115 CUT
38125 12 1.25 27.4 1240 CUT
38165 16 1.6 30.6 1660 CUT
38205 20 1.6 33.7 1930 CUT
38245 24 2 37.8 2485 CUT
38305 30 2 39.7 2790 CUT
Cross Section :0.75
3817 1 0.9 12.1 290 CUT
3827 2 0.9 17 470 CUT
3837 3 0.9 18 545 CUT
3847 4 0.9 19.3 625 CUT
3857 5 1.25 21.5 835 CUT
3867 6 1.25 23.2 945 CUT
3877 7 1.25 23.1 990 CUT
38107 10 1.6 29.1 1480 CUT
38127 12 1.6 29.9 1610 CUT
38167 16 1.6 32.8 1915 CUT
38207 20 2 37 2500 CUT
38247 24 2 40.9 2900 CUT
38307 30 2.5 44.2 3680 CUT
Cross Section :1.0
38110 1 0.9 12.5 310 CUT
38210 2 0.9 18 520 CUT
38310 3 0.9 18.8 595 CUT
38410 4 0.9 20.2 685 CUT
38510 5 1.25 22.6 930 CUT
38610 6 1.25 24.3 1030 CUT
38710 7 1.25 24.3 1085 CUT
381010 10 1.6 30.5 1640 CUT
381210 12 1.6 31.6 1785 CUT
381610 16 1.6 34.5 2135 CUT
382010 20 2 38.9 27.85 CUT
382410 24 2.5 44.1 3620 CUT
383010 30 2.5 46.5 4115 CUT
           
Code No. of Triple Armour Wire Diameter External Diameter Cable weight Packing*
.No
    N x mm² .approx nominal .approx  
  mm mm kg/km  
Cross Section :1.5
38115 1 0.9 13.4 350 CUT
38215 2 0.9 19.2 590 CUT
38315 3 0.9 20.1 690 CUT
38415 4 1.25 22.6 945 CUT
38515 5 1.25 24.3 1080 CUT
38615 6 1.25 26.3 1220 CUT
38715 7 1.25 26.3 1295 CUT
381015 10 1.6 33.1 1930 CUT
381215 12 1.6 34.1 2120 CUT
381615 16 2 38.4 2835 CUT
382015 20 2.5 44 3790 CUT
382415 24 2.5 48 4340 CUT
383015 30 2.5 50.6 4910 CUT
Cross Section :2.5
38125 1 0.9 14.7 430 CUT
38225 2 1.25 22.6 880 CUT
38325 3 1.25 23.8 1020 CUT
38425 4 1.25 25.8 1210 CUT
38525 5 1.6 28.6 1555 CUT
38625 6 1.6 31 1770 CUT
38725 7 1.6 31 1875 CUT
381025 10 2 39.4 2820 CUT
381225 12 2 41 3135 CUT
381625 16 2.5 46.1 4190 CUT
382025 20 2.5 50.9 4955 CUT
382425 24 3.15 57.8 6480 CUT
383025 30 3.15 61 7330 CUT
*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length`
Technical data
Flame Temperature Range MUTUAL CAPACITY (Max) Insulation  Thickness (Nom) Insulation  Resistance (Min) Conductor Resistance class2(Max)
  Propagation
IEC 60332-3-24 -30ºC~+70ºC (FIXED LAYING) pF/m mm2   mm MΩxKm Ω/km mm2
VDE 0482-332-3-24
EN 60332-3-24
BS EN 60332-3-24 250 0.5 0.6 100 36 0.5
0.75 0.6 24.5 0.75
1 0.6 18.1 1
1.5 0.6 12.1 1.5
2.5 0.7 7.41 2.5
 
Bending Radius Test Voltage Operating Voltage Current L/R(Ratio) (Max)
Load(25ºC)
7, 5 X Cable Ø C r. /C r. =2 0 0 0 V 300/500V A mm2 µH /Ω mm2
Cr./Scrn.=2000 V 6 0.5 25 0.5
13 0.75 25 0.75
16 1 25 1
20 1.5 40 1.5
25 2.5 60 2.5
Temperature Range               Fixed -40 °C to+70 °C ; During Installation -5 °C -+50 °C
Flame Test                                  IEC/EN/BS/DIN 60332-1-2 (VDE 0482-332-1-2)
Design Standards
IEC 60092-376
EN 50288-7
DIN VDE 819-7

 

Conductor   Annealed Copper or Tinned Copper - Class 2 Acc to IEC 60228 / HD 383 / DIN VDE 0295
Insulation PVC acc to EN 50290-2
Insulation Color Code Pair : white, Black (numbered)
Triple :White, Black , Red (Numbered)
Ind. Screen  PES Tape +TINNED COPPER DRAIN WIRE; AL-PES TAPE
Overall Screen TINNED COPPER DRAIN WIRE; AL-PES TAPE
Inner Sheath EN 50290-2 PVC Compound
Armour Galvanized Round Steel Wire
Sheathing PVC compound Type YM1 UV Resistant and Flame retardant Acc to EN 0290-2
Color Black, Red, Blue Or by resuest


 

Cable with protective screen against electromagnetic impacts, for reliable and quick (up to 200 kB/s) transmission of analogue and digital signals, suitable for fixed and mobile installations in process control and data processing systems, mostly in chemical and petrochemical industrial plants and electric power plants. Low values of signal attenuation and low mutual capacitance enable large-distance signal transmission. Laid in dry and damp premises, also outdoor, in air or ground. Not intended for supply purposes