PHONE : 982144972925-7+

NYRY

2 Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RE/RM/SM .nom .Nom .nom mm mm .Nom  
  mm mm mm kg/km  
422150 2x 1.5 RM 0.8 1.8 8.2 0.9 13.7 360 CUT
422151 2x 1.5 RE 0.8 1.8 7.6 0.9 12.9 320 CUT
422250 2x2.5 RM 0.8 1.8 9.1 0.9 14.5 370 CUT
422251 2x2.5 RE 0.8 1.8 8.7 0.9 13.4 350 CUT
42240 2x 4 RM 1,0 1.8 11.3 0.9 16.4 520 CUT
42241 2x 4 RE 1,0 1.8 10.8 0.9 15 410 CUT
42260 2x 6 RM 1,0 1.8 12.3 1.25 18.2 650 CUT
421261 2x 6 RE 1,0 1.8 11.8 1.25 16.4 480 CUT
422100 2x 10 RM 1,0 1.8 14.3 1.25 20.1 600 CUT
422101 2x 10 RE 1,0 1.8 13.5 1.25 18.3 510 CUT
422160 2x 16 RM 1,0 1.8 16.3 1.25 22.3 600 CUT
42261 2x 16 RE 1,0 1.8 14.6 1.25 19.1 510 CUT
42225 2x 25 RM 1,2 1.8 19.5 1.6 26.2 960 CUT
42235 2x 35 RM 1,2 1.8 20.7 1.6 27.5 1350 CUT
42250 2x 50 SM 1,4 1.9 21.2 1.6 28.1 1670 CUT
42270 2x 70 SM 1,4 2 24.2 2 32.1 1845 CUT
42295 2x 95 SM 1,6 2.2 28.1 2 36.6 2310 CUT
422120 2x 120 SM 1,6 2.3 31.1 2 39.6 3145 CUT
422150 2x 150 SM 1,8 2.4 34.2 2.5 44.2 3865 CUT
422185 2x 185 SM 2,0 2.6 38.1 2.5 48.6 4640 CUT
422240 2x 240 SM 2,2 2.8 43.1 2.5 53.7 6090 CUT
422300 2x 300 SM 2,4 2.9 48.1 2.5 59.6 7360 CUT
422400 2x 400 SM 2,6 3.1 54.2 2.5 65.4 10820 CUT
.Code No  number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RE/RM/SM .nom .Nom .nom mm mm .Nom  
  mm mm mm kg/km  
423150 3x 1.5 RM 0.8 1.8 8.9 0.9 14.4 400 CUT
423151 3x 1.5 RE 0.8 1.8 8.1 0.9 14 380 CUT
423250 3x2.5 RM 0.8 1.8 9.8 0.9 15.3 460 CUT
423251 3x2.5 RE 0.8 1.8 9.1 0.9 15 450 CUT
42340 3x 4 RM 1,0 1.8 11.8 1.25 17.8 700 CUT
42341 3x 4 RE 1,0 1.8 11.1 1.25 17.1 680 CUT
42360 3x 6 RM 1,0 1.8 13 1.25 19.5 830 CUT
42361 3x 6 RE 1,0 1.8 12.2 1.25 18.9 800 CUT
423100 3x 10 RM 1,0 1.8 15.1 1.25 21.3 1050 CUT
423101 3x 10 RE 1,0 1.8 14.6 1.25 20.9 1010 CUT
423160 3x 16 RM 1,0 1.8 17.4 1.25 23.6 1360 CUT
42316 3x 16 RE 1,0 1.8 16.8 1.25 23.1 1340 CUT
42325 3x 25 RM 1,2 1.8 21.1 1.6 27.9 1990 CUT
42335 3x 35 RM 1,2 1.8 22.2 1.6 29.1 2300 CUT
42350 3x 50 SM 1,4 2 24.1 2 31.6 2800 CUT
42370 3x 70 SM 1,4 2.1 27.8 2 35.9 3810 CUT
42395 3x 95 SM 1,6 2.2 31.6 2 40.1 4770 CUT
423120 3x 120 SM 1,6 2.3 34.3 2 42.8 5650 CUT
423150 3x 150 SM 1,8 2.5 38.6 2.5 48.6 7280 CUT
423185 3x 185 SM 2,0 2.7 42.3 2.5 52.8 8650 CUT
423240 3x 240 SM 2,2 2.9 47.8 2.5 58.9 10730 CUT
423300 3x 300 SM 2,4 2.9 49.1 2.5 60.8 12600 CUT
                   
4 Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RE/RM/SM .nom .Nom .nom mm mm .Nom  
  mm mm mm kg/km  
424150 4x 1.5 RM 0.8 1.8 9.7 0.9 15.1 445 CUT
424151 4x 1.5 RE 0.8 1.8 9.1 0.9 14.8 430 CUT
424250 4x2.5 RM 0.8 1.8 10.6 0.9 16.2 530 CUT
424251 4x2.5 RE 0.8 1.8 10.1 0.9 15.8 510 CUT
42440 4x 4 RM 1,0 1.8 13.1 1.25 19.2 810 CUT
42441 4x 4 RE 1,0 1.8 12.8 1.25 18.9 980 CUT
42460 4x 6 RM 1,0 1.8 14.2 1.25 20.6 950 CUT
42461 4x 6 RE 1,0 1.8 13.9 1.25 20.1 930 CUT
424100 4x 10 RM 1,0 1.8 16.5 1.25 22.8 1230 CUT
424101 4x 10 RE 1,0 1.8 16.1 1.25 22.3 1210 CUT
424160 4x 16 RM 1,0 1.8 19.3 1.6 25.9 1750 CUT
42416 4x 16 RE 1,0 1.8 19 1.6 25.3 1710 CUT
42425 4x 25 RM 1,2 1.8 23.7 1.6 30.3 2360 CUT
42435 4x 35 RM 1,2 1.9 24.6 1.6 31.9 2770 CUT
42450 4x 50 SM 1,4 2.1 27.1 2 35.8 3700 CUT
42470 4x 70 SM 1,4 2.2 30.5 2 39.1 4720 CUT
42495 4x 95 SM 1,6 2.4 35.1 2.5 44.9 6380 CUT
424120 4x 120 SM 1,6 2.5 38.6 2.5 48.3 7610 CUT
424150 4x 150 SM 1,8 2.7 42.8 2.5 53.3 9150 CUT
424185 4x 185 SM 2,0 2.9 47.3 2.5 58.4 10950 CUT
424240 4x 240 SM 2,2 3.1 53.2 2.5 64.5 13620 CUT
424300 4x 300 SM 2,4 3.3 58.9 2.5 70.6 16420 CUT
                   
5 Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RE/RM/SM .nom .Nom .nom mm mm .Nom    
  mm mm mm kg/km    
425150 5x 1.5 RM 0.8 1.8 10.5 0.9 16.1 510 CUT  
425151 5x 1.5 RE 0.8 1.8 10.2 0.9 15.7 495 CUT  
425250 5x2.5 RM 0.8 1.8 11.9 0.9 17.3 605 CUT  
425251 5x2.5 RE 0.8 1.8 11.5 0.9 16.9 590 CUT  
42540 5x 4 RM 1,0 1.8 14.4 1.25 20.6 920 CUT  
42541 5x 4 RE 1,0 1.8 14.1 1.25 20.1 900 CUT  
42560 5x 6 RM 1,0 1.8 15.9 1.25 21.8 1100 CUT  
42561 5x 6 RE 1,0 1.8 15.6 1.25 21.3 1080 CUT  
425100 5x 10 RM 1,0 1.8 18.4 1.6 25.3 1560 CUT  
425101 5x 10 RE 1,0 1.8 18.1 1.6 25.1 1540 CUT  
425160 5x 16 RM 1,0 1.8 21.3 1.6 28.3 2050 CUT  
42516 5x 16 RM 1,0 1.8 21 1.6 28 2010 CUT  
42525 5x 25 RM 1,2 1.9 25.8 1.6 32.9 2820 CUT  
42535 5x 35 RM 1,2 2 27.6 2 35.6 3560 CUT  
42550 5x 50 RM 1,4 2.2 32.5 2 40.8 4700 CUT  
42570 5x 70 RM 1,4 2.3 36.9 2 45.9 6030 CUT  
42595 5x 95 RM 1,6 2.5 42.6 2.5 52.1 8270 CUT  
425120 5x 120 RM 1,6 2.7 46.8 2.5 56.8 9890 CUT  
425150 5x 150 RM 1,8 2.9 52.6 2.5 62.8 12010 CUT  
425185 5x 185 RM 2,0 3 57.7 2.5 68.3 14290 CUT  
425240 5x 240 RM 2,2 3.3 65.1 2.5 77.1 18870 CUT  
*)Packing: CUT= cable in different lengths on drum or reel, possible cutting at required 
Temperature during installation: -5 °C up to +50 °C
fixed installedTemperature: -30 °C up to +70 °C
Temperature at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3,5 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:  
single core: 15D
multi core: 12D
Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: PVC compound, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, with or without protective yellow-green conductor
Bedding PVC compound 
Armour: a layer of thin round galvanized steel wires
Sheath: PVC compound
sheath color: black
Izvedba.jpg

Distribution and signal power cable for static application, mostly in ground, but also in water, within and outside facilities, in cable canals, in concrete. Used in electric power plants and other electric plants, in industry, metropolitan networks and for connection of signalling devices in industry, traffic and similar. Resistant to mechanical loads, able to sustain heavier mechanical tensile strains, could be laid slantingly or vertically, same as on grounds exposed to land-sliding.