NAYY

NAYY
  • Cable With IEC Standard
  • Cable Suitable For Direct Burial
  • UV Resistant
  • cable for use in water
  • Max Conductor Temperature 70 'C
  • Min Installation Temperature -5°C
  • Flame Retardant
Cable Code  number of cores x conductor cross-section Construction External diameter Insulation thickness Sheath thickness Conductor resistance at 20 °C Short circuit current 1s Cable weight Packing*
      min - max. nom. nom. max. nom. kg/km  
  N x mm²   mm mm mm Ω/km kA  
A1150 1 x 50 RM 14 - 17 1,4 1,8 0,641 3,80 298 CUT
A1170 1 x 70 RM 16 - 19 1,4 1,8 0,443 5,32 383 CUT
A1195 1 x 95 RM 18 - 21 1,6 1,8 0,320 7,22 490 CUT
A11120 1 x 120 RM 19 - 22 1,6 1,8 0,253 9,12 575 CUT
A11150 1 x 150 RM 21 - 25 1,8 1,8 0,206 11,40 695 CUT
A11185 1 x 185 RM 23 - 27 2,0 1,8 0,164 14,10 845 CUT
A11240 1 x 240 RM 26 - 30 2,2 1,8 0,125 18,20 1100 CUT
A11300 1 x 300 RM 28 - 32 2,4 1,9 0,100 22,80 1379 CUT
A11400 1 x 400 RM 32 - 37 2,6 2,0 0,0778 27,20 1615 CUT
A11500 1 x 500 RM 35 - 40 2,8 2,1 0,0605 34,00 2015 CUT
A11630 1 x 630 RM 41 - 45 2,8 2,2 0,0469 42,84 2472 CUT
   
A1416 4 x 16 RM 21 - 25 1,0 1,8 1,91 1,21 750 CUT
A1425 4 x 25 RM 25 - 32 1,2 1,8 1,200 1,90 950 CUT
A1435 4 x 35 RM 27 - 34 1,2 1,8 0,868 2,66 1141 CUT
A1450 4 x 50 SM 29 - 36 1,4 1,9 0,641 3,80 1242 CUT
A1470 4 x 70 SM 33 - 40 1,4 2,1 0,443 5,32 1631 CUT
A1495 4 x 95 SM 38 - 45 1,6 2,2 0,320 7,22 2063 CUT
A14120 4 x 120 SM 41 - 49 1,6 2,4 0,253 9,12 2538 CUT
A14150 4 x 150 SM 46 - 54 1,8 2,5 0,206 11,40 3090 CUT
A14185 4 x 185 SM 51 - 59 2,0 2,7 0,164 14,10 3838 CUT
A14240 4 x 240 SM 57 - 65 2,2 2,9 0,125 18,20 4863 CUT
Temperature during installation: -5 °C up to +50 °C
fixed installed Temperature : -30 °C up to +70 °C
Temperature at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3.5 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 30 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:  
single core: 15D
multi core: 12D
Conductor: Cu, class 1 or 2 acc. to  IEC 60228 / DIN VDE 0295
class 2: multi wire stranded, round (RM) or sector (SM)
Insulation: PVC compound Type A acc. to IEC 60502-1, concentrically stranded cores, color marked acc to VDE 0293-308, with or without protective yellow-green conductor
Filler: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVC compound ST1 acc. to IEC 60502-1
sheath colour: black
Izvedba.jpg

Distribution power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in industrial plants, metropolitan networks and in other electric plants.