PHONE : 982144972925-7+

NA2XY

Single Core
Code No. number of cores x conductor cross-section Construction Construction of individual conductor External diameter Insulation thickness Cable weight Packing*
      nominal .Nom .nom .Nom  
  Nx mm²   nx mm mm mm kg/km  
A1110 1x 10 RM 7x 1.35 8.4 0.7 85 CUT
A1116 1x 16 RM 7x 1.7 9.4 0.7 115 CUT
A1125 1x 25 RM 7x 2,2 11.1 0.9 160 CUT
A1135 1x 35 RM 7x 2,6 11.7 0.9 200 CUT
A1150 1x 50 RM 19x 1,8 13.1 1 260 CUT
A1170 1x 70 RM 19x 2,2 15.1 1.1 340 CUT
A1195 1x 95 RM 19x 2,6 16.6 1.1 430 CUT
A11120 1x 120 RM 19x 2,8 17.3 1.2 500 CUT
A11150 1x 150 RM 37x 2,3 20.6 1.4 640 CUT
A1185 1x 185 RM 37x 2,6 22.5 1.6 790 CUT
A11240 1x 240 RM 37x 2,95 25.8 1.7 1,010 CUT
A11300 1x 300 RM 61x 2,6 27.9 1.8 1,210 CUT
A11400 1x 400 RM 61x 2,89 31.2 2 1,700 CUT
A11500 1x 500 RM 61x 3,23 34.8 2.2 1,990 CUT
A11630 1x 630 RM 91x 2,97 42.1 2.4 2,480 CUT

 

2 Core
Code No. number of cores x conductor cross-section Construction Insulation thickness sheath  thickness External diameter Cable weight Packing*
      .nom .Nom .nom .Nom  
  Nx mm²   mm mm mm kg/km  
A1210 2x 10 RM 0.7 1.8 16.2 350 CUT
A1216 2x 16 RM 0.7 1.8 18.7 460 CUT
A1225 2x 25 RM 0.9 1.8 22.1 590 CUT
A1235 2x 35 RM 0.9 1.8 23.3 740 CUT
A1250 2x 50 SM 1 1.8 20.9 840 CUT
A1270 2x 70 SM 1.1 1.8 23.8 1,100 CUT
A1295 2x 95 SM 1.1 2 27.2 1,440 CUT
A12120 2x 120 SM 1.2 2.1 30.2 1,740 CUT
A12150 2x 150 SM 1.4 2.2 33.4 2,040 CUT
A12185 2x 185 SM 1.6 2.3 36.8 2,600 CUT
A12240 2x 240 SM 1.7 2.5 41.5 3,215 CUT
A12300 2x 300 SM 1.8 2.7 46 3,950 CUT

 

3 Core
Code No. number of cores x conductor cross-section Construction Insulation thickness sheath  thickness External diameter Cable weight Packing*
      .nom .Nom .nom .Nom  
  N x mm²   mm mm mm kg/km  
A1310 3x 10 RM 0.7 1.8 17 285 CUT
A1316 3x 16 RM 0.7 1.8 19.7 510 CUT
A1325 3x 25 RM 0.9 1.8 23.4 660 CUT
A1335 3x 35 RM 0.9 1.8 24.6 830 CUT
A1350 3x 50 SM 1 1.8 24.2 950 CUT
A1370 3x 70 SM 1.1 1.9 27.8 1,130 CUT
A1395 3x 95 SM 1.1 2 31 1,430 CUT
A13120 3x 120 SM 1.2 2.1 34.3 1,720 CUT
A13150 3x 150 SM 1.4 2.3 38.4 2,115 CUT
A13185 3x 185 SM 1.6 2.4 42.5 2,580 CUT
A13240 3x 240 SM 1.7 2.6 47.5 3,280 CUT
A13300 3x 300 SM 1.8 2.8 49.5 3,970 CUT

 

4 Core
Code No. Dimensions – number of cores x conductor cross-section Construction Insulation thickness sheath  thickness External diameter Cable weight Packing*
      .nom .Nom .nom .Nom  
  N x mm²   mm mm mm kg/km  
A14325/16 3x 25/16 RM/RM 0.9 1.8 24.5 650  CUT
A14335/16 3x 35/16 RM/RM 0.9 1.8 26 850  CUT
A14350/25 3x 50/25 Sm/RM 1 1.8 25.7  950 CUT
A14370/35 3x 70 /35 SM/RM 1.1 1.9 29.4  1330 CUT
A14395/50 3x 95 /50 SM/SM 1.1 2.1 33.1  1750 CUT
A143120/70 3x 120 /70 SM/SM 1.2 2.2 36.7  2100 CUT
A143150/70 3x 150/70 SM/SM 1.4 2.3 40.9 2600  CUT
A143185/95 3x 185/95 SM/SM 1.6 2.5 45.4  3200 CUT
A143240/120 3x 240/120  SM/SM 1.7 2.7 50.8  4050 CUT
A143300/150 3x 300/150 SM/SM 1.8 2.8 56  4750 CUT
A1410 4X 10 RM 0.7 1.8 18.4 450 CUT
A1416 4X 16 RM 0.7 1.8 21.4 605 CUT
A1425 4X 25 RM 0.9 1.8 25.5 790 CUT
A1435 4X 35 RM 0.9 1.8 26.9 995 CUT
A1450 4X 50 SM 1 1.9 27 1,060 CUT
A1470 4X 70 SM 1.1 2 30.9 1,435 CUT
A1495 4X 95 SM 1.1 2.1 34.5 1,820 CUT
A14120 4X 120 SM 1.2 2.3 38.5 2,275 CUT
A14150 4X 150 SM 1.4 2.4 42.9 2,750 CUT
A14185 4X 185 SM 1.6 2.6 47.6 3,340 CUT
A14240 4X 240 SM 1.7 2.8 53.2 4,250 CUT
A14300 4X 300 SM 1.8 3 58.9 5,135 CUT

 

5 Core
.Code No Dimensions – number of cores x conductor cross-section Construction Insulation thickness sheath  thickness External diameter Cable weight Packing*
      .nom .Nom .nom .Nom  
  N x mm²   mm mm mm kg/km  
A1510 5X 10 RM 0.7 1.8 20 525 CUT
A1516 5X 16 RM 0.7 1.8 23.3 710 CUT
A1525 5X 25 RM 0.9 1.8 27.9 935 CUT
A1535 5X 35 RM 0.9 1.8 29.5 1,190 CUT
A1550 5X 50 RM 1 2 34 1,480 CUT

 

 

 

 

Temperature during installation: -5 °C up to +50 °C
fixed installed Temperature : -20 °C up to +90 °C
Temperature at short circuit of max. 5 s: up to 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3.5 kV AC
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 30 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:  
single core: 15D
multi core: 12D

 

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area DC Resistance at 20°C AC Resistance at 90°C
in air in ground
(mm²) Max. (Ω/km) Max. (Ω/km) (mH/km) Max. (A) Max. (A) Max. (kA)
10 3.08 3.949 0.248 67 75 0.94
16 1.91 2.449 0.236 91 100 1.5
25 1.2 1.539 0.242 119 128 2.35
35 0.868 1.113 0.234 147 154 3.29
50 0.641 0.822 0.232 179 183 4.7
70 0.443 0.568 0.229 227 226 6.58
95 0.32 0.411 0.224 277 270 8.93
120 0.253 0.325 0.223 322 308 11.28
150 0.206 0.265 0.225 364 344 14.1
185 0.164 0.211 0.225 425 391 17.39
240 0.125 0.162 0.223 501 454 22.56
300 0.1 0.13 0.222 574 511 28.2
Conductor: Al, class 1 or 2 acc. to  IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: XLPE-compound DIX 3 acc. to HRN HD 603 S1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308
Filler: (in multi wire cables) extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVCST1 acc to IEC 60502-1
sheath colour: black
Izvedba.jpg

Distribution and signal power cable for static application in ground, in water, within facilities, in cable canals, in concrete, where heavier mechanical stresses are not expected, and the cable has to be protected against mechanical damages, also in conditions where cables are not exposed to heavier tensile strains. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants where heavier current and thermal loads are expected (operating temperature of conductor up to 90 °C).