NA2XRY

2Core

Code No. number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RM/SM nom. Nom. nom. mm mm Nom.  
  mm mm mm kg/km  
A3210 2 x 10 RM 0.7 1.8 13.0 1.25 19.1 655 CUT
A3216 2 x 16 RM 0.7 1.8 15.1 1.25 21.2 820 CUT
A3225 2 x 25 RM 0.9 1.8 18.5 1.6 25.3 1125 CUT
A3235 2 x 35 RM 0.9 1.8 19.7 1.6 26.5 1325 CUT
A3250 2 x 50 SM 1.0 1.8 19.3 1.6 26.1 1530 CUT
A3270 2 x 70 SM 1.1 2.0 22.1 1.6 29.4 1923 CUT
A3295 2 x 95 SM 1.1 2.1 25.6 2.0 33.8 2595 CUT
A32120 2 x 120 SM 1.2 2.2 28.4 2.0 36.8 3020 CUT
A32150 2 x 150 SM 1.4 2.3 31.4 2.0 40.0 3430 CUT
A32185 2 x 185 SM 1.6 2.5 35 2.5 45.0 4650 CUT
A32240 2 x 240 SM 1.7 2.7 39.3 2.5 49.7 5460 CUT
A32300 2 x 300 SM 1.8 2.8 43.8 2.5 54.4 6360 CUT

 

3Core
Code No. Dimensions – number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RM/SM nom. Nom. nom. mm mm Nom.  
  mm mm mm kg/km  
A3310 3 x 10 RM 0.7 1.8 13.8 1.25 19.9 720 CUT
A3316 3 x 16 RM 0.7 1.8 16.1 1.25 22.2 890 CUT
A3325 3 x 25 RM 0.9 1.8 19.7 1.6 26.6 1230 CUT
A3335 3 x 35 RM 0.9 1.8 21 1.6 27.8 1480 CUT
A3350 3 x 50 SM 1.0 1.9 22.6 1.6 29.6 1550 CUT
A3370 3 x 70 SM 1.1 2.0 26.4 2.0 34.4 2185 CUT
A3395 3 x 95 SM 1.1 2.2 29.4 2.0 37.8 2590 CUT
A33120 3 x 120 SM 1.2 2.3 32.5 2.0 41.1 3010 CUT
A33150 3 x 150 SM 1.4 2.5 36.6 2.5 46.6 3960 CUT
A33185 3 x 185 SM 1.6 2.6 40.5 2.5 50.7 4570 CUT
A33240 3 x 240 SM 1.7 2.8 45.5 2.5 56.1 5510 CUT
A33300 3 x 300 SM 1.8 3.0 47.1 2.5 58.1 6405 CUT

 

4Core
Code No. Dimensions – number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RM/SM nom. Nom. nom. mm mm Nom.  
  mm mm mm kg/km  
A3410 4 x 10 RM 0.7 1.8 15.2 1.25 21.3 800 CUT
A3416 4 x 16 RM 0.7 1.8 17.8 1.6 24.6 1160 CUT
A3425 4 x 25 RM 0.9 1.8 21.9 1.6 28.7 1405 CUT
A3435 4 x 35 RM 0.9 1.9 23.3 1.6 30.3 1750 CUT
A3450 4 x 50 SM 1 2 25.2 1.6 32.4 1850 CUT
A3470 4 x 70 SM 1.1 2.2 29.3 2 37.7 2630 CUT
A3495 4 x 95 SM 1.1 2.3 32.6 2 41.3 3150 CUT
A34120 4x 120 SM 1.2 2.5 36.7 2.5 46.7 4160 CUT
A34150 4 x 150 SM 1.4 2.6 40.9 2.5 51.1 4920 CUT
A34185 4 x 185 SM 1.6 2.8 45.2 2.5 55.8 5660 CUT
A34240 4 x 240 SM 1.7 3 50.8 2.5 61.8 6805 CUT
A34300 4 x 300 SM 1.8 3.2 56.1 2.5 67.5 7930 CUT
A342516 3 x 25/16 Rm/rm 0.9 1.8 20.9 1.6 27.9 1487 CUT
A343516 3 x 35/16 Rm/rm 0.9 1.8 21.9 1.6 28.8 1722 CUT
A345025 3 x 50/25 Sm/rm 1 1.9 24.2 1.6 31.2 2440 CUT
A347035 3 x 70/35 Sm/rm 1.1 2.1 27.8 2 36.4 2950 CUT
A349550 3 x 95/50 Sm/sm 1.1 2.2 31.3 2 39.8 4033 CUT
A34240120 3 x 240/120 Sm/sm 1.7 2.9 48.6 2.5 62.1 8162 CUT
A34300150 3 x 300/150 Sm/sm 1.8 3 53.5 2.5 69.2 9318 CUT

 

5Core
Code No. number of cores x conductor cross-section Construction Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RE/RM/SM nom. Nom. nom. mm mm Nom.  
  mm mm mm kg/km  
A3510 5 x 10 RM 0.7 1.8 16.8 1.25 22.9 920 CUT
A3516 5 x 16 RM 0.7 1.8 19.7 1.6 26.5 1320 CUT
A3525 5 x 25 RM 0.9 1.8 24.3 1.6 31.1 1620 CUT
A3535 5 x 35 RM 0.9 1.9 25.9 1.6 32.9 1980 CUT
A3550 5 x 50 RM 1 2.2 30 2 38.3 2650 CUT

*) Packing: CUT= cable in different lengths on drum or reel, possible cutting at required 

Temperature during installation: -5 °C up to +50 °C
fixed installed Temperature: -20 °C up to +90 °C
at short circuit of max. 5 s: up to 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3.5 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius: 12D

 

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area DC Resistance at 20°C AC Resistance at 90°C
in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA)
10
3.08 3.949 0.248 71 78 0.94
16
1.91 2.449 0.236 95 102 1.5
25
1.2 1.539 0.242 125 131 2.35
35
0.868 1.113 0.234 154 158 3.29
50
0.641 0.822 0.232 186 187 4.7
70
0.443 0.568 0.229 235 229 6.58
95
0.32 0.411 0.224 288 274 8.93
120
0.253 0.325 0.223 333 312 11.28
150
0.206 0.265 0.225 375 347 14.1
185
0.164 0.211 0.225 437 394 17.39
240
0.125 0.162 0.223 513 455 22.56
300
0.1 0.13 0.222 585 511 28.2
*Further information about rating factor for certain cable arrangement can be found on supplementary technical information
Conductor: Al, class 2 acc. to IEC 60228 / DIN VDE 0295
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: XLPE compound (cross-linked polyethylene),
Bedding: spouted elastomer or plastomer compound or wrapped thermoplastic tapes
Armour: a layer of thin round galvanized steel wires
Sheath:

PVC compound

Color : Black (Ral 9005) or By request

Distribution and signal power cable for static application, mostly in ground, but also in water, within and outside facilities, in cable canals, in concrete. Used in electric power plants and other electric plants, in industry, metropolitan networks and for connection of signalling devices in industry, traffic and similar. Resistant to mechanical loads, able to sustain heavier mechanical tensile strains, could be laid slantingly or vertically, same as on grounds exposed to land-sliding.