PHONE : 982144972925-7+

N2XRY

2Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RM/SM .nom .nom .Nom .nom mm mm .Nom  
  mm mm mm mm kg/km  
442150 2x 1.5 RM 0.7 0.7 1.8 8.1 0.9 13.5 350 CUT
442250 2x2.5 RM 0.7 0.7 1.8 8.9 0.9 14.3 395 CUT
44240 2x 4 RM 0.7 0.7 1.8 10 0.9 15.4 470 CUT
44260 2x 6 RM 0.7 0.7 1.8 11.1 0.9 16.5 560 CUT
442100 2x 10 RM 0.7 0.7 1.8 13 1.25 19.1 825 CUT
442160 2x 16 RM 0.7 0.7 1.8 15.1 1.25 21.2 1,080 CUT
44225 2x 25 RM 0.9 0.9 1.8 18.5 1.6 25.3 1,575 CUT
44235 2x 35 RM 0.9 0.9 1.8 19.7 1.6 26.5 1,810 CUT
44250 2x 50 SM 1 1 1.8 19.3 1.6 26.1 1,900 CUT
44270 2x 70 SM 1.1 1.1 2 22.1 1.6 29.4 2,440 CUT
44295 2x 95 SM 1.1 1.1 2.1 25.6 2 33.8 2,325 CUT
442120 2x 120 SM 1.2 1.2 2.2 28.4 2 36.8 3,955 CUT
442150 2x 150 SM 1.4 1.4 2.3 31.4 2 40 4,730 CUT
442185 2x 185 SM 1.6 1.6 2.5 35 2.5 45 6,055 CUT
442240 2x 240 SM 1.7 1.7 2.7 39.3 2.5 49.7 7,350 CUT
442300 2x 300 SM 1.8 1.8 2.8 43.8 2.5 54.4 8,815 CUT
442400 2x 400 SM 2 2 3.1 49.8 2.5 61 11,200 CUT
 
3Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RE/RM/SM .nom .nom .Nom .nom mm mm .Nom  
  mm mm mm mm kg/km  
443150 3x 1.5 RM 0.7 0.7 1.8 8.5 0.9 13.9 375 CUT
443250 3x2.5 RM 0.7 0.7 1.8 9.4 0.9 14.8 435 CUT
44340 3x 4 RM 0.7 0.7 1.8 10.6 0.9 16 525 CUT
44360 3x 6 RM 0.7 0.7 1.8 11.8 0.9 17.2 635 CUT
443100 3x 10 RM 0.7 0.7 1.8 13.8 1.25 19.9 945 CUT
443160 3x 16 RM 0.7 0.7 1.8 16.1 1.25 22.2 1,235 CUT
44325 3x 25 RM 0.9 0.9 1.8 19.7 1.6 26.6 1,840 CUT
44335 3x 35 RM 0.9 0.9 1.8 21 1.6 27.8 2,150 CUT
44350 3x 50 SM 1 1 1.9 22.6 1.6 29.6 2,575 CUT
44370 3x 70 SM 1.1 1.1 2 26.4 2 34.4 3,595 CUT
44395 3x 95 SM 1.1 1.1 2.2 29.4 2 37.8 4,465 CUT
443120 3x 120 SM 1.2 1.2 2.3 32.5 2 41.1 5,340 CUT
443150 3x 150 SM 1.4 1.4 2.5 36.6 2.5 46.6 6,925 CUT
443185 3x 185 SM 1.6 1.6 2.6 40.5 2.5 50.7 8,185 CUT
443240 3x 240 SM 1.7 1.7 2.8 45.5 2.5 56.1 10,190 CUT
443300 3x 300 SM 1.8 1.8 3 47.1 2.5 58.1 11,980 CUT
 
4Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  Nx mm² RM/SM .nom .nom .Nom .nom mm mm .Nom  
  mm mm mm mm kg/km  
444150 4x 1.5 RM 0.7 0.7 1.8 9.3 0.9 14.7 420 CUT
444250 4x2.5 RM 0.7 0.7 1.8 10.3 0.9 15.7 470 CUT
44440 4x 4 RM 0.7 0.7 1.8 11.6 0.9 17 605 CUT
44460 4x 6 RM 0.7 0.7 1.8 13 1.25 19.1 840 CUT
444100 4x 10 RM 0.7 0.7 1.8 15.2 1.25 21.3 1110 CUT
444160 4x 16 RM 0.7 0.7 1.8 17.8 1.6 24.6 1610 CUT
44425 4x 25 RM 0.9 0.9 1.8 21.9 1.6 28.7 2185 CUT
44435 4x 35 RM 0.9 0.9 1.9 23.3 1.6 30.3 2605 CUT
44450 4x 50 SM 1 1 2 25.2 1.6 32.4 3200 CUT
4470 4x 70 SM 1.1 1.1 2.2 29.3 2 37.7 4465 CUT
44495 4x 95 SM 1.1 1.1 2.3 32.6 2 41.3 5585 CUT
444120 4x 120 SM 1.2 1.2 2.5 36.7 2.5 46.7 7220 CUT
444150 4x 150 SM 1.4 1.4 2.6 40.9 2.5 51.1 8670 CUT
444185 4x 185 SM 1.6 1.6 2.8 45.2 2.5 55.8 10345 CUT
444240 4x 240 SM 1.7 1.7 3 50.8 2.5 61.8 12895 CUT
444300 4x 300 SM 1.8 1.8 3.2 56.1 2.5 67.5 15540 CUT
4442516 3x 25/16 Rm/rm 0.9 0.9 1.8 20.9 1.6 27.9 2030 CUT
4443516 3x 35/16 Rm/rm 0.9 0.9 1.8 21.9 1.6 28.8 2350 CUT
4445025 3x 50/25 Sm/rm 1 1 1.9 24.2 1.6 31.2 2905 CUT
4447035 3x 70/35 Sm/rm 1.1 1.1 2.1 27.8 2 36.4 4060 CUT
4449550 3x 95/50 Sm/sm 1.1 1.1 2.2 31.3 2 39.8 5060 CUT
44412070 3x 120/70 Sm/sm 1.2 1.2 2.4 34.5 2 43.5 6200 CUT
44415070 3x 150/70 Sm/sm 1.4 1.4 2.5 39.2 2.5 49.2 7820 CUT
44418595 3x 185/95 Sm/sm 1.6 1.6 2.7 43.2 2.5 53.6 9360 CUT
4442412 3x 240/120 Sm/sm 1.7 1.7 2.9 48.6 2.5 59.4 11630 CUT
4443015 3x 300/150 Sm/sm 1.8 1.8 3 53.5 2.5 64.5 13970 CUT
 
5Core
.Code No  number of cores x conductor cross-section Construction Insulation thickness Insulation thickness sheath  thickness Diameter under Armour Armour wire Diameter External diameter Cable weight Packing*
  N x mm² RE/RM/SM .nom .nom .Nom .nom mm mm .Nom  
  mm mm mm mm kg/km  
445150 5x 1.5 RM 0.7 0.7 1.8 10.2 0.9 15.6 460 CUT
445250 5x2.5 RM 0.7 0.7 1.8 11.3 0.9 16.7 555 CUT
44540 5x 4 RM 0.7 0.7 1.8 12.8 1.25 18.9 800 CUT
44560 5x 6 RM 0.7 0.7 1.8 14.3 1.25 20.4 965 CUT
445100 5x 10 RM 0.7 0.7 1.8 16.8 1.25 22.9 1285 CUT
445160 5x 16 RM 0.7 0.7 1.8 19.7 1.6 26.5 1860 CUT
44525 5x 25 RM 0.9 0.9 1.8 24.3 1.6 31.1 2580 CUT
44535 5x 35 RM 0.9 0.9 1.9 25.9 1.6 32.9 3075 CUT
44550 5x 50 RM 1 1 2.2 30 2 38.3 4375 CUT
44570 5x 70 RM 1.1 1.1 2.3 35.2 2 43.8 5715 CUT
44595 5x 95 RM 1.1 1.1 2.4 39.9 2.5 49.7 7705 CUT
445120 5x 120 RM 1.2 1.2 2.6 44.5 2.5 54.6 9325 CUT
445150 5x 150 RM 1.4 1.4 2.8 49.6 2.5 60.1 11260 CUT
445185 5x 185 RM 1.6 1.6 3 55.4 2.5 66.4 13600 CUT
445240 5x 240 RM 1.7 1.7 3.2 62.4 3.2 75.1 17805 CUT
Temperature during installation: -5 °C up to +50 °C
fixed installed Temperature: -20 °C up to +90 °C
Temperature at short circuit of max. 5 s: up to 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3.5 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:  
single core: 15D
multi core: 12D
Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: PVC compound, concentrically stranded cores, color marked acc. to HRN HD 308 S2 / VDE 0293-308, with or without protective yellow-green conductor
Bedding: PVC compound
Armour: galvanized steel wires
Sheath: PVC compound Acc to IEC 60502-1
sheath colour: black
Izvedba.jpg

Distribution and signal power cable for static application, mostly in ground, but also in water, within and outside facilities, in cable canals, in concrete. Used in electric power plants and other electric plants, in industry, metropolitan networks and for connection of signalling devices in industry, traffic and similar. Resistant to mechanical loads, able to sustain heavier mechanical tensile strains, could be laid slantingly or vertically, same as on grounds exposed to land-sliding.(Operating Temperature of conductor up to 90ºC)