Bare Copper Conductor

Rope weight Conductor resistance at 20 °C Permitted stress External diameter Construction Calculated cross-sections Dimensions – number of cores x conductor cross-section Code 
No.
nominal max. max. approx. nominal      
kg/km Ω/km kN mm n x mm mm² mm²  
90 18,072 4,02 4,1 7x1,35 10,02 10 10
142 11,385 6,37 5,1 7x1,70 15,89 16 16
217 0,7460 09,72 6,3 7x2,10 24,25 25 25
308 0,5265 13,77 7,5 7x2,50 34,36 35 35
443 0,3656 19,84 9,0 7x3,00 49,48 50 501
433 0,3759 19,38 9,0 19x1,80 48,35 50 502
590 0,2762 26,38 10,5 19x2,10 65,81 70 70
836 0,1949 37,39 12,5 19x2,50 93,27 95 951
834 0,1949 37,39 12,5 37x1,79 93,11 95 952
1048 0,1554 46,90 14,0 19x2,80 116,99 120 1201
1052 0,1554 46,90 14,1 37x2,01 117,40 120 1202
1318 0,1238 58,98 15,8 37x2,25 147,11 150 150
1627 0,1003 72,81 17,5 37x2,50 181,52 185 185
2173 0,0753 97,23 20,3 61x2,25 242,54 240 240
2683 0,0610 120,04 22,5 61x2,50 299,43 300 300
3585 0,0456 160,42 26,0 61x2,89 400,14 400 400
4479 0,0365 200,38 29,1 61x3,23 499,83 500 500

Zarcable  supplies a range of bare copper conductors, which are ideally suited for use in electrical grounding systems and on insulators for overhead line transmission and distribution applications. In particular, our Class 2 stranded bare copper wire manufactured in accordance with BS EN 13602 and BS EN 60228 (formerly BS6360) offers greater flexibility than solid, hard-drawn wire. Hard drawn stranded copper conductors offers greater flexibility than a solid, hard-drawn wire.
 
Our bare copper conductors are principally used in energy transmission installations to maximise thermal and electrical conductivity, and to transmit energy with optimal efficiency. This uninsulated wire can be used as an earthing cable. The copper also offers natural resistance against environmental stresses such as wet, humid, and saline climates.