PHONE : 982144972925-7+

A-2Y(ST)2YRY

 

Code No.   Diameter Under Armor Armour wire Diameter External diameter Sheath thickness Cable weight Packing
cores x conductor diameter
    Approx.   Approx. nominal approx.  
  N x mm² mm mm mm mm kg/km  
Conductor size : 0.6 mm
23226 2 x 2 x 0,6 5.9 0.9 10.5 1.4 205 CUT
23426 4 x 2 x 0,6 6.7 0.9 11.1 1.4 240 CUT
23626 6 x 2 x 0,6 7.5 0.9 12.2 1.4 275 CUT
231026 10 x 2 x 0,6 9.2 0.9 13.8 1.4 350 CUT
231526 15 x 2 x 0,6 10.9 0.9 15.7 1.6 450 CUT
232026 20 x 2 x 0,6 11.9 1.6 17.2 1.6 520 CUT
233026 30 x 2 x 0,6 14.2 1.6 19.1 1.6 640 CUT
235026 50 x 2 x 0,6 17.5 1.8 23.5 1.8 1035 CUT
2310026 100 x 2 x 0,6 23.7 2 30.9 2 1820 CUT
2315026 150 x 2 x 0,6 28.5 2 36.8 2.2 2640 CUT
2320026 200 x 2 x 0,6 32.1 2 40.8 2.2 3185 CUT
Conductor size : 0.8 mm
23228 2 x 2 x 0,8 6.9 0.9 11.5 1.4 245 CUT
23428 4 x 2 x 0,8 7.8 0.9 12.4 1.4 305 CUT
23628 6 x 2 x 0,8 9 0.9 13.8 1.4 355 CUT
23828 8 x 2 x 0,8 9.7 0.9 14.5 1.4 405 CUT
231028 10 x 2 x 0,8 11.2 0.9 15.8 1.4 465 CUT
231528 15 x 2 x 0,8 13.1 0.9 17.8 1.4 570 CUT
232028 20 x 2 x 0,8 14.5 1.3 20.2 1.6 805 CUT
232528 25 x 2 x 0,8 15.8 1.3 21.2 1.6 895 CUT
233028 30 x 2 x 0,8 17.1 1.3 22.4 1.6 985 CUT
235028 50 x 2 x 0,8 21.7 1.6 28.2 1.6 1580 CUT
2310028 100 x 2 x 0.8 29.8 2 37.2 1.8 2810 CUT
Temperature range
During Installation 5°C up to +50°C
Fixed Installed -30°C up to +70°C
Storage Temperature 40°C
Mechanical And Electrical Specifications
Operationg Voltage 300V
Test Voltage core/core U eff. 1500 V
Bending Radius 10XD
Insulation Resistance Min 5000MΩXKm
Mutual Resistance Max 55 nF/km
Capacitance Umbalance 0.6=250PF
0.8=160PF
Flame Behavior Acc to IEC 60332-1
Cable Standard Generally as IEC 60708
Conductor Anealed Copper Class1 (0.6 , 0.8mm).
Insulation PE Acc to EN 50290
Insulation Color Code ACC to  IEC 60708
Seperator Polyester Tspe
Screen PS tape+ Al/PS Tape+ Drain Wire
Beddign LDPE
Atmour Galvanized Steel Wire
Sheath PVC Compound
Sheath Color Blac

Cable with protective screen against electromagnetic impacts, for reliable and quick (up to 200 kB/s) transmission of analogue and digital signals, suitable for fixed and mobile installations in process control and data processing systems, mostly in chemical and petrochemical industrial plants and electric power plants. Low values of signal attenuation and low mutual capacitance enable large-distance signal transmission. Steel wire armour ensures resistance to mechanical damages. Laid in dry and damp premises, also outdoor, in air or ground. Not intended for supply purposes.